    ZYS-P10AD Surge Protective Device is a self-protected device specially designed to be used in outdoor and commercial LED lighting fixtures for transient overvoltage protection. It is mainly composed of varistor and gas discharge tube device.It is designed to protect electrical devices from electrical surges and voltage spikes.External installation,can be replaced independently,easy to install and maintai 

    Application: Digital Signage /Traffic Lighting /Flood Lighting/Tunnel Lighting /Street lighting /Wall Lamp/Road Lighting /Parking Lighting /AC-LED Lighting

    Agency Standard Agency File Number

    Features

    Applicable to class I or II lamps

    Built in protection mode: L-N, L-PE, N-PE

    Built in thermal separation function for higher security

    Parallel isolation design, excellent protection performance

    Excellent surge resistance and very low residual voltage

    1*1.0 Electronic wire

    Small and convenient for embedded installation

    IP66 dust proof and waterproof grade

    Parameters

    Part Number ZYS-P10AD
    Rated working voltage/Un(VAC) 100-277V
    Maximum continuous working voltage/MCOV/Uc(VAC)(1) 320V
    Rated load current/IL(A) /
    Nominal discharge current/In(kA)(2) 5KA
    Maximum Discharge Current/Imax(kA)(3) 10KA
    Surge Impulse Voltage/Uoc(KV) 10KV
    Voltage Protection Level/Up(V)(4) L-N,N-G/PE≤1.5KV,L-G/PE≤2.5KV
    Power Supply System TN
    Waterproof grade IP66
    Work environment -40℃~+85℃
    UL1449 test classification Type 5

    Notes

    (1) Maximum continuous working voltage MCOV/UC(VAC): The maximum continuous working voltage continuously applied to the SPD line end
    (2) Nominal discharge current (In) (kA): The measured value of SPD withstand capability; the measured value of 15 pulses using 8/20us current waveform.
    (3) Maximum discharge current (max) (kA):The maximum discharge current is the measured value of the SPD's maximum withstand capability, and the measured value of 2 pulses using 8/20us current waveform
    (4) Voltage protection level/Up: IEC61643-11 voltage protection level, the maximum residual voltage measured value of the nominal discharge current (ln) under continuous application of 8/20u pulses, is the maximum voltage measured value after one round